This product is discontinued

SYSCREW 490 WATER EVO CO

Art. no.: CWWE490CO

Technical feature

• 15 sizes

• Cooling capacity from 444 to 1567 [kW] - CO units

• Cooling capacity from 383to 1342 [kW] - HP units

• Heating capacity from 488 to 1715 [kW] - HP units

• Cooling capacity from 386 to 1357 [kW] - RC units

• One refrigerant circuits (from 440 to 770 size)

• Two refrigerant circuits (from 860 to 1550 size)

• Twin screw compressors

• Shell & tubes heat exchangers

• Available versions: CO (Cooling only), HP (Heat Pump - reverse cycle water side), RC (Remote condenser unit), BC (Brine version)

• Acoustic versions: - (Basic Low Noise), S (Super Low Noise)

 

Standard features

• Phase sequence control

• Electronic expansion valve

• Control circuit transformer

• Control data logger

• Modbus protocol kit for BMS

 

Factory installed options

• Lonwork protocol kit for BMS (RS485 / ETHERNET)

• Bacnet protocol kit for BMS (RS485 / ETHERNET)

• Compressor soft-starter

• Double set-point

• Power factor correction capacitors

• GSM

• Automatic circuit breaker

• HP & LP gauges

• Compressor suction valves

• Compressor suction valves

• Compressor oil level switch

• Compressor liquid injection

• Compressor stepless control

• Cu/Ni condensers

• Condensers for well application

• Desuperheater

• Total heat recovery (TR)

 

Field installed accessories

• Remote ON/OFF control

• Remote keyboard panel

• Sequencer, up to max four units

• Anti-vibration spring

• Water flow switch

• Water pressure switch

• Water filter

• Remote hydro kits with buffer tank, 1 or 2 low or high pressure pump(s), relevant accessories and with or without antifreeze heater

In stock earliest delivery 29.02.19 Show availability
  • Aug 29, 2018
  • Sep 09, 2018
  • 500
  • 500

Technical parameter

Performances
Cooling capacity 494.4 kW
EER 5.05 W/W
General data
Frequency 50 Hz
Phase(s) 3~
Voltage (Nominal) 400 V
Sound data
Sound pressure level at 1m, outdoor unit 77 dB(A)
Dimensions and weights
Weight 0 kg
NOTES

1

Evaporator water inlet victaulic connection

2

Evaporator water outlet victaulic connection

3

Condenser water outlet victaulic connection

4

Condenser water inlet victaulic connection

P1, P2, P3, P4

AVM position

Size

A

B

C

D

E

F

dia 1-2

dia 3-4

440-490

650

2410

560

3620

130

350

DN 150 (6”)

DN 100 (4”)

570

680

2980

550

4210

180

325

DN 150 (6”)

DN 125 (5”)

630

680

2980

550

4210

210

335

DN 150 (6”)

DN 125 (5”)

700-770

720

2860

600

4180

210

335

DN 200 (8”)

DN 125 (5”)

Document filename Document filetype
CD_SyScrew_440-770 Water_EVO.DWG CAD-file