Topvex TX/C06-L-CAV

Item Number: 94480

• Topvex is delivered with the Access control system

• Space saving top connection

• High efficient counter-flow heat exchanger

- > 80% dry efficiency (EN 308) at nominal airflow

- No mixing of extract and supply air

- Automatic summer operating

- Cool recovering

• Section defrosting

-

The Topvex counter flow unit TX/C (-S

*

) are pre-configured units with Section defrosting

• Low energy use

- Energy efficient plug fans with EC motors

• Large inspection doors for easy maintenance

-

All main components are easy removable

- Separate electrical cabinet facilitates commissioning and service

• Manufactured in Aluzinc plated sheet metal (AZ185)

- Corrosive class C4 (Industrial and coastal areas with moderate salinity)

- AZ185 sheet metal has more than 50 years of technical lifetime

• Factory tested

Topvex TX/C is designed for meeting the coming energy demands with high heat recovery efficiency and low energy use. To guarantee the high heat recovery efficiency the exchanger is designed for low air speed and by that also a low pressure drop. The supply and extract air filter are designed to have a low pressure drop, without compromising with the filtration efficiency. A low internal pressure drop is essential to keep the energy use down Topvex TX/C features Plug fans with EC technology to ensure high efficiency. The EC-motors has when speed-controlled, 15-20% lower energy consumption compared to a standard frequency controlled asynchrony motor.

100% By-pass of heat exchanger secures lowest possible internal pressure drop during the warm season.

A damper isolates the exchanger during the warm period ensures that there is no undesirable heat recovering.

Constant air volume control is standard and Variable air volume control is available as an accessory.

The Topvex counter flow unit TX/C with item name ending -S are pre-configured units with Section defrosting.

The Section defrosting consist of a pre-wired sectioned damper that divides the heat exchanger in three areas plus the by-pass section. All sections are controlled by individual motors for each section and are connected to a separate, pre-programmed control unit.

Section defrosting will prevent severe ice built up in the heat exchanger and allow defrosting of the heat exchanger, while still providing heat recovery through the defrosting sequence.

When activated by pressure detecting, the damper sections will be cyclic operated. Each section will operate in sequence and compensate low temperature in the exhaust air, by modulating the by-pass and section damper.

Topvex is delivered with the new Access control system. The system includes NaviPad control panel, featuring an easy-to-use intuitive HTML5 user interface.

The protection class of the NaviPad control panel is IP54 and 0-50 C° permitted temperature. The enclosure is not UV resistant and the NaviPad is not for outdoor mounting. Communication between the panel and the controller in the cabinet is possible with up to 100 meters of cable.

The NaviPad is connected via 3 meters flat cable. It is mounted on the Topvex unit or on the wall, easy to detach for handheld use.

Relevant operating data and settings are available in real time and can be changed with a few clicks.

Access control has built-in energy saving features like free cooling, cooling recovery, season related temperatures and airflow control.

Possibility to edit names for the unit, the alarms and control components gives the user options to adapt to different installations needs.

With the system overview dashboard it is possible to monitor several air handling units within a local network.

Standard communication possibilities are: Modbus RTU via RS-485 & TCP/IP & BACnet via IP.

Ordering code.

- Model: TX/C03, TX/C04 and TX/C06.

- Heating coil:

EL

(Electric).

HWL

(Hot water coil-low power).

HWH

(Hot water coil-high power).

None

(No heater).

- Right or Left model: R

(Right),

L

(Left). The side where the supply air is located when viewed from the access side.

- Airflow control: CAV

(Constant air volume).

-

Airflow control (accessory):

VAV

(Variable air volume = constant duct pressure control).

-Section defrosting:

-S

(Section defrosting).

*

Section defrosting is available for all Topvex TX/C. Units with item name ending -S are Section defrosting configured.

I.e. Topvex TX/C03 EL-L-CAV-S.

Ecodesign

Product
Trade name Systemair
Product name Topvex TX/C06
Ecodesign
ErP compliance 2018
Unit category NRVU
Unit type BVU
Drive Integrated VSD
Heat recovery type Recuperative
Temperature ratio 80.6 %
qv nom 0.6 m³/s
P nom 1.058 kW
SFPint 1,042 W/(m³/s)
Face velocity 1.4 m/s
Ps nom 200 Pa
Ps int. Supply 238 Pa
Ps int. Extract 352 Pa
Supply fan efficiency 49.8 %
Extract fan efficiency 62.4 %
External Leakage 2 %
Internal Leakage 1 %
Filter energy performance 1,587 kWh
Sound power level LWA 56 dB(A)

Technical parameters

Unit
Frequency 50 Hz
Voltage (nominal) 400 V
Phase(s) 3~
Recommended fuse 3x10 A
Enclosure class IP23
Speed regulation Stepless
Air flow 170 to 850 L/s
Supply fan
Voltage 400 V
Phase(s) 3~
Input power (P1), supply fan 895 W
Supply air filter
Filter class, supply air ePM1 60%
Extract air filter
Filter class, extract air ePM10 60%
Heat exchanger
Exchanger type Exchanger flow
Heater
Heating type None
Return fan / Extract fan
Voltage 400 V
Phase(s) 3~
Input power, extract fan 895 W
Others
Fan control CAV, air flow control; Stepless voltage control
Installation placement Vertical
Supply side Left
Dimensions and weights
Weight 398 kg
ErP
ErP ready ErP 2018

Supply

Extract

A B C D E F G H I J K L M

Topvex TX/C06

2150

1630

880

1998

725

116

196

324

140

600

197

300

1065

BFT TX/C06 Filter Coarse 50% Item Number: 209932 BFT TX/C06 Filter Coarse 50% .
BFT TX/C06 Filter ePM1 60% Item Number: 209930 BFT TX/C06 Filter ePM1 60% .
BFT TX/C06 Filter ePM10 60% Item Number: 209931 BFT TX/C06 Filter ePM10 60% .
CO2RT-R-D Transmitter Item Number: 6993 CO2RT-R-D Transmitter .
Corrigo exp. module CEM15 Item Number: 209554 Corrigo exp. module CEM15 .
CTTG 400 Roof curb Item Number: 27253 CTTG 400 Roof curb .
CTVX 400 Combi-roof hood Aluz. Item Number: 27246 CTVX 400 Combi-roof hood Aluz. .
CTVX 400 Combi-roof hood Black Item Number: 27242 CTVX 400 Combi-roof hood Black .
CVVX 400 Combi grille white Item Number: 146262 CVVX 400 Combi grille white .
CVVX 400 Combi grille, black Item Number: 6236 CVVX 400 Combi grille, black .
DS 60-30 Flexible connection Item Number: 1547 DS 60-30 Flexible connection .
DXRE 60-35-3-2,5 Duct cooler Item Number: 7956 DXRE 60-35-3-2,5 Duct cooler .
F-T120 Timer frame Item Number: 5137 F-T120 Timer frame .
LDR 60-30 Silencer Item Number: 5072 LDR 60-30 Silencer .
LDR-B 60-30 Silencer, baffle Item Number: 9240 LDR-B 60-30 Silencer, baffle .
NaviPad extension cable 10m Item Number: 316350 NaviPad extension cable 10m .
PGK 60-35-3-2,0 Duct cooler Item Number: 6612 PGK 60-35-3-2,0 Duct cooler .
PKIS3G-600x300-DV7-T Item Number: 70786 PKIS3G-600x300-DV7-T .
Preheat.kit Topvex RB60-30 EL Item Number: 131043 Preheat.kit Topvex RB60-30 EL .
Presence detector/IR24-PC Item Number: 7288 Presence detector/IR24-PC .
Push button, impulse Item Number: 9693 Push button, impulse .
Safety switch BWS 416 TPSN Item Number: 206735 Safety switch BWS 416 TPSN .
Safety switch OTP16T3M 3-pole Item Number: 213042 Safety switch OTP16T3M 3-pole .
Safety switch OTP16T4M 4-pole Item Number: 213044 Safety switch OTP16T4M 4-pole .
Systemair-1 CO2 duct sensor Item Number: 14906 Systemair-1 CO2 duct sensor .
Systemair-1M CO2 duct sensor Item Number: 14908 Systemair-1M CO2 duct sensor .
Systemair-2 CO2 duct sensor Item Number: 14907 Systemair-2 CO2 duct sensor .
Systemair-E CO2 sensor Item Number: 14904 Systemair-E CO2 sensor .
Systemair-E-D CO2 sensor Item Number: 14905 Systemair-E-D CO2 sensor .
T 120 Timer Item Number: 5165 T 120 Timer .
TG-AH1/PT1000 Contact Sensor Item Number: 7899 TG-AH1/PT1000 Contact Sensor .
TG-KH/PT1000 Duct sensor Item Number: 202705 TG-KH/PT1000 Duct sensor .
TG-R5/PT1000 Room sensor 0-50° Item Number: 5404 TG-R5/PT1000 Room sensor 0-50° .
TG-UH/PT1000 Wall sensor Item Number: 35203 TG-UH/PT1000 Wall sensor .
TUNE-AHU-SE003-600x300-TF24 Item Number: 79896 TUNE-AHU-SE003-600x300-TF24 .
UG3-A4O Smoke detector Item Number: 15043 UG3-A4O Smoke detector .
VAV Air Volume Control Item Number: 145946 VAV Air Volume Control .
VBR 60-30-2 Water heating batt Item Number: 5466 VBR 60-30-2 Water heating batt .
VOC Duct sensor Item Number: 156813 VOC Duct sensor .
VOC Room sensor Item Number: 156812 VOC Room sensor .
Water-lock Item Number: 206263 Water-lock .