Item Number: 88380
Main features:
• High energy-efficiency counter flow heat exchanger with EC - technology fans
• Demand control regulation with the built-in humidity sensor
• Automatic defrosting
• Built in electrical pre-heater is available as accessory
• SAVE Touch control with a touch display and Startup Wizard for easy commissioning
• Connection board for easy access and connection of accessories
• Modbus communication RS-485 as standard
• Internet access module is available as accessory
A heat recovery unit designed for ventilated areas up to approximately 240 m2.
Left and right handed models are available.
SAVE VTC 300 is designed for installation on the wall in a laundry room or storeroom.
SAVE VTC 300 is a unit with white painted double skinned panels and comes with complete control functionality. The unit is equipped with a high efficiency counter flow heat exchanger. Energy efficient fans with EC motors as well as low-pressure filters reduce the energy consumptions and gives low SFP factor (Specific Fan Power) and low sound. The built in humidity sensor in extract air can be used for demand control.
All settings and features are accessible via the SAVE Touch control panel which is integrated in the front door. The panel is a color touch screen with a user friendly interface. The option for connecting one or more external control panels is available. In addition, control panel has separate user level for authorized installers and service personnel.
The home screen displays information such as airflow, temperature, air quality and active functions. You can select between MANUAL and AUTO mode or choose preferred settings from the pre-configured user modes.
SAVE Touch AUTO mode has many functions available that regulate the airflow according to CO2, presence, humidity, schedule etc. The demand function control gives effective and economical operation to ensure best indoor air quality.Alarm symbols indicate possible malfunctions and issues direct alerts if anything needs to be rectified.
The unit has an automatic defrosting function with 3 different modes to choose from, depending on the indoor environment as well as the outdoor conditions.
Without preheater, the unit works down to -5°C in tight houses / passive houses where unbalanced airflow is not allowed. When unbalance is allowed, without preheater the unit works down to -15°C. Below -15°C, a preheater is always needed.
SAVE VTC 300 can be supplemented with a re-heater battery.
External connection board that has prewired inputs and outputs allows easy installation and setup of external sensors as well as external heaters / coolers and other accessories.
The unit comes with low-pressure pleated filters:
• Supply air filter G4/Coarse 65%
• Extract air filter G4/Coarse 65%
Pleated filter F7/ePM1 60% for supply air is available as an accessory. Pleated filter M5/ePM10 50% is available as an accessory for extract air filtering.
| Product | ||
|---|---|---|
| Trade name | Systemair | |
| Product name | SAVE VTC 300 R |
| Basic unit | ||
|---|---|---|
| ErP compliance | 2018 | |
| SEC Average | -36.6 | kWh/(m².a) |
| SEC Cold | -79.5 | kWh/(m².a) |
| SEC Warm | -11.9 | kWh/(m².a) |
| SEC Class | A | |
| Unit category | RVU | |
| Unit type | BVU | |
| Drive | Integrated VSD | |
| Heat recovery type | Recuperative | |
| Temperature ratio | 85 | % |
| qv max | 381 | m³/h |
| P max | 174 | W |
| Sound power level LWA | 40 | dB(A) |
| qv ref | 0.074 | m³/s |
| Ps ref | 50 | Pa |
| SPI | 0.35 | kW/(m³/h) |
| CTRL | 0.85 | |
| MISC | 1.1 | |
| x-value | 2 | |
| External Leakage | 2 | % |
| Internal Leakage | 1 | % |
| Type of product | RAHU/AAHE | |
| AEC average | 362 | kWh |
| AEC cold | 900 | kWh |
| AEC warm | 317 | kWh |
| AHS Average | 4,494 | kWh/a |
| AHS Cold | 8,792 | kWh/a |
| AHS Warm | 2,032 | kWh/a |
| Units with local demand control | ||
|---|---|---|
| ErP compliance | 2018 | |
| SEC Average | -40.8 | kWh/(m².a) |
| SEC Cold | -84.7 | kWh/(m².a) |
| SEC Warm | -15.7 | kWh/(m².a) |
| SEC Class | A | |
| Unit category | RVU | |
| Unit type | BVU | |
| Drive | Integrated VSD | |
| Heat recovery type | Recuperative | |
| Temperature ratio | 85 | % |
| qv max | 381 | m³/h |
| P max | 174 | W |
| Sound power level LWA | 40 | dB(A) |
| qv ref | 0.074 | m³/s |
| Ps ref | 50 | Pa |
| SPI | 0.35 | kW/(m³/h) |
| CTRL | 0.65 | |
| MISC | 1.1 | |
| x-value | 2 | |
| External Leakage | 2 | % |
| Internal Leakage | 1 | % |
| Type of product | RAHU/AAHE | |
| AEC average | 230 | kWh |
| AEC cold | 768 | kWh |
| AEC warm | 185 | kWh |
| AHS Average | 4,590 | kWh/a |
| AHS Cold | 8,979 | kWh/a |
| AHS Warm | 2,075 | kWh/a |
| Energy class, Basic unit | ||
|---|---|---|
![]() |
| Energy class, Local demand | ||
|---|---|---|
![]() |
| Product | ||
|---|---|---|
| Voltage (nominal) | 230 | V |
| Frequency | 50 | Hz |
| Phase(s) | 1~ | |
| Air flow | 300 | m³/h |
| Recommended fuse | 10 A | |
| Enclosure class | IP24 |
| Exchanger | ||
|---|---|---|
| Exchanger type | Exchanger flow |
| Heater | ||
|---|---|---|
| Heating type | None |
| Supply air | ||
|---|---|---|
| Input power, supply fan | 85 | W |
| Extract air | ||
|---|---|---|
| Input power, extract fan | 85 | W |
| Filter | ||
|---|---|---|
| Filter class, supply air | Coarse 65% | |
| Filter class, extract air | Coarse 65% |
| Color casing | ||
|---|---|---|
| Color casing, RAL | RAL 9010 |
| Dimensions and weights | ||
|---|---|---|
| Weight | 72 | kg |
| Used for | ||
|---|---|---|
| Installation placement | Vertical | |
| Supply side | Right |
| ErP | ||
|---|---|---|
| Energy class, Basic unit | A | |
| Energy class, Local demand | A | |
| ErP ready | ErP 2016; ErP 2018 |
| 1 | Outdoor air |
|
2 |
Supply air |
|
3 |
Extract air |
|
4 |
Exhaust air |
| * Inspection hatch | ||
|
** Drainage |