Símbolo ECOM Símbolo ECOM

SHR1200

Side duct connection HRV,1053 CFM

Item Number: 99272

• Airflow up to 1219 cfm @ 0.4" PS
• Push-pull configuration
• Removable screw terminal for easy connection
• Dual service doors & reversible electrical box
• External three position switch (Low/Standby/High)
Application

The SHR 1200 Commercial Heat Recovery Ventilation system (HRV) complements today's tight buildings.

How it works

Fantech Heat Recovery Ventilators (HRV) are designed to supply air into a building while exhausting an equal amount of contaminated air to the outside. The aluminum heat exchanger core transfers sensible energy between air streams resulting in tempering of the supply air and reduced loads on the HVAC system.

Defrost cycle

A preset defrost sequence is activated at an outdoor air temperature of 23°F and lower. During the defrost sequence, the supply blower shuts down & the exhaust blower switches to high speed to maximize the effectiveness of the defrost strategy. The unit then returns to normal operation, and continues the cycle.

Parametros tecnicos

Unidad
Frecuencia 60 Hz
Tensión (nominal) 120 V
Fase(s) 1~
Corriente de entrada 11.17 A
MCA 13.75 A
MOP 15 A
Potencia de entrada 1,340 W
Caudal de aire máximo 1,218 cfm
Presion estatica 0.4 in.wg
Dimensiones y pesos
Peso 114.5 kg
Certificados
Certificado CSA, AHRI
Images Wiring - SHR1200 - Systemair Images Wiring - SHR1200 - Systemair
Supply Temperature Net Airflow Net Effectiveness

Sensible

Total

°F (°C)

cfm (L/s)

%

%

Heating

35 (1.7)

1035 (488)

57

37

35 (1.7)

776 (366)

61

40

Cooling

95 (35)

1035 (488)

47

18

95 (35)

776 (366)

49

19

Images Dimensions - SHR1200 - Systemair
A B C D E F G I J K Drain Spout

51 2/5 (1306)

47 1/5 (1199)

20 (508)

3 (76)

8 (203)

8 (203)

36 1/4 (921)

22 (559)

32 1/2 (826)

1/2 (13)

Dimensional information is in inches (mm)

Fans

Four (4) factory balanced fans with backward curved blades. Motors come with permanently lubricated sealed ball bearings, (TOP) thermal overload protected and maintenance-free operation.

Heat recovery core

Fantech manufactures this fixed plate cross-flow heat exchanger using new 1100 alloy aluminum. Heat exchanger is engineered with a turbulence inducing geometry in order to maximize heat transfer while allowing an effective evacuation of condensate. The plates are hemmed and sealed to ensure no cross-contamination of airstreams. The aluminum core had a plastic handle for easy removal. The SHR 1200 features three cores, each 12" x 12" (305 mm x 305 mm) with a 15" (380 mm) depth.

Defrost

A preset frost control sequence is initiated if the outdoor temperature falls below the set point of 23°F (-5°C). During the initial stage, the supply blower shuts down & the exhaust blower switches into high speed to eliminate frost build-up in the core. The unit then returns to normal operation for the final stage of the frost control sequence at which time the sequence is repeated if the outdoor air temperatures is still below the set point.

Serviceability

Cores, filters and drain pan can be accessed easily from both sides of the HRV from hinged access panels. Cores conveniently slide out with only 15" (380 mm) clearance. Blowers can be accessed from both side of the HRV from fastened access panels. Blowers are easily removed by taking off the access panel and sliding the motor plates out of the HRV. A quick connect allows for fast inspection of blowers.

Case

22 gauge galvanized steel. Baked powder coated paint.

Insulation

Insulated with 1in. (25 mm) fiberglass with FSK facing for condensation control.

Filters

The exhaust and fresh air streams are protected by MERV1 washable filters constructed to meet UL 900. Optional MERV6 filters are direct replacement to the MERV1. Use of MERV6 filters will add an additional system pressure of 0.76 in.wg (190 Pa) at 1200 cfm (566 l/s). Additional MERV Rated filters available upon request.

Controls

External three (3) position (Low/Stand By/High) rocker switch that will offer continuous ventilation. In addition Fantech offers a variety of external controls.

Mounting

Unit may be suspended by using threaded rod, not supplied, or placed on a platform. Unit shall be adaptable for easy service of electrical components.

Warranty

Limited lifetime on aluminum core, 3 years on motors, and 3 years on parts.

Requirements and standards
• Complies with the UL 1812 requirements regulating the construction and installation of Heat Recovery Ventilators
• Complies with the CSA C22.2 no. 113 Standard applicable to ventilators
• Technical data was obtained from published results of test relating to AHRI 1060 Standards
BPM0820 - Systemair Item Number: 99301 BPM0820

3-way bypass module for recirculation, 8"x20" duct

.
CO2RT-R Transmitter - Systemair Item Number: 99315 CO2RT-R Transmitter

0-2000ppm w/relay, room mounting

.
EDF1 Control multi fuincion - Systemair Item Number: 40375 EDF1 Control multi fuincion

EDF1 Control multi fuincion

.
EDF7 Elec Multi-Funct Dehum - Systemair Item Number: 44883 EDF7 Elec Multi-Funct Dehum

Electronic Multi-Function Dehumidistat

.
EFD 20-8, Damper, TFB24 - Systemair Item Number: 99304 EFD 20-8, Damper, TFB24

20"x8" Shutter damper with spring-return actuators, 24V

.
IR 4 Compuerta tipo iris - Systemair Item Number: 411234 IR 4 Compuerta tipo iris

IR 4 Compuerta tipo iris

.
IR 5 Compuerta tipo iris - Systemair Item Number: 411235 IR 5 Compuerta tipo iris

IR 5 Compuerta tipo iris

.
IR 6 Compuerta tipo iris - Systemair Item Number: 411236 IR 6 Compuerta tipo iris

IR 6 Compuerta tipo iris

.
IR 8 Compuerta tipo iris - Systemair Item Number: 411237 IR 8 Compuerta tipo iris

IR 8 Compuerta tipo iris

.
MGE 4 Difusor de extracción - Systemair Item Number: 411106 MGE 4 Difusor de extracción

MGE 4 Difusor de extracción

.
MGE 5 Difusor de extracción - Systemair Item Number: 411370 MGE 5 Difusor de extracción

MGE 5 Difusor de extracción

.
MGE 6 Difusor de extracción - Systemair Item Number: 411371 MGE 6 Difusor de extracción

MGE 6 Difusor de extracción

.
MGE 8 Difusor de extracción - Systemair Item Number: 411244 MGE 8 Difusor de extracción

MGE 8 Difusor de extracción

.
RTS2 Control ERV/HRV - Systemair Item Number: 40164 RTS2 Control ERV/HRV

RTS2 Control ERV/HRV

.
RTS5, 20/40/60 min timer - Systemair Item Number: 44794 RTS5, 20/40/60 min timer

RTS5, 20/40/60 min timer

.