X-KTEX 50-30-4 Rect.fan (ATEX)

Numéro article: 1566

Certified according to ATEX directive 94-9 EC

Speed controllable

Integral thermistors (PTC *)

Maintenance-free and reliable

KTEX fans can be installed in any position and are easy to connect using the DS flexible connections. These fans have impellers with forward-curved blades and external rotor motors. The casing is manufactured from galvanised sheet steel, with a copper inlet cone. To protect the motor from overheating, PTC protective circuits in the motors must be connected to a monitoring apparatus certified according to Directive 94/9/EC that isolates the motor from voltage supply immediately when activated. We recommend to use UEK230E

for motor protection.

Explosion proof versions comply with EN 60079-0:2009, EN 14986:2007, EN 60079-7:2007. Improved safety in accordance with

Ex e IIB+H2 T3 Gb

* Positive Temperature Coefficient

Paramètres techniques

Données nominales
Tension nominale 400 V
Fréquence 50 Hz
Phase(s) [~] 3~
Puissance installée 900 W
Intensité 1,8 A
Vitesse de rotation 1 355 tr/min
Débit d'air max 2 376 m³/h
Pression statique 140 Pa
Température air en mouvement max 40 °C
Temp. max. avec variateur 40 °C
Données acoustiques
Niveau sonore à 3 m (20m² Sabine) 58 dB(A)
Protection/Classification
Indice de protection, moteur IP44
Classe d'isolation F
Certificat SP 03ATEX3103X
Régulations et sondes
Plage de température, ambiante et conduit -20 à 40 °C
Dimensions et poids
Rectangulaire, hauteur, entrée 300 x 500 mm
Rectangulaire, largeur, entrée 300 x 500 mm
Rectangulaire, hauteur, sortie 300 x 500 mm
Rectangulaire, largeur, sortie 300 x 500 mm
Poids 21,9 kg
Autres
Type de connexion Rectangulaire
Type de moteur AC

Circular duct fan for easy

 

and direct installation in ducts.

 

Galvanized steel sheet housing. Copper inlet cone. Service cover. The fan unit is mounted on the service cover for easy cleaning and maintenance.

 

Free-running, forward curved circular impeller made of galvanized steel sheet.

 

Impeller acc. to VDI 2060, balancing quality G 6.3, dynamically balanced in two planes.

 

Explosion proof, voltage controllable external rotor motor.

 

(IP44), maintenance-free, the motor is placed inside the air flow for cooling. PTC with leads to a motor protection device (e.g. Systemair U-EK 230E-IP54). Speed-controlled via a 5-step transformer.

 

Supply cable, led out.

 

Suitable to transport explosive atmospheres of the zone 1. category 2G and zone 2, category 3G. The fans are applicable for zone 1 and 2 and for temperature classes T1, T2, and T3. Ignition type "e" increased safety EExe II, T3.

 

Tested acc. to ATEX Directive 94-9-EC.

 

Conformity with EN 50014, EN 50019, EN 13463-1 and EN 1127-1.

 

For indoor installation.

 

Installation in any mounting position.

 

R-DK4 KT Auto-transformateur - Systemair Numéro article: 6051 R-DK4 KT Auto-transformateur

Auto-transformateur 5 vitesses triphasé (400V+N) 4A

.
RTRD 4 Auto-transformateur - Systemair Numéro article: 5942 RTRD 4 Auto-transformateur

Auto-transformateur triphasé 5 vitesses 4A

.
RTRDU 4 Auto-transformateur - Systemair Numéro article: 5946 RTRDU 4 Auto-transformateur

Auto-transformateur triphasé 2x5 vit. 4A

.
U-EK230E Protection Moteur EX - Systemair Numéro article: 30199 U-EK230E Protection Moteur EX

Termistor Motor protection ATEX approved

.
FFK 50-30 Cassette sans filtre - Systemair Numéro article: 1755 FFK 50-30 Cassette sans filtre

Caisson filtration rectangulaire pour filtre à poches

.
LDR 50-30 Silencieux - Systemair Numéro article: 5071 LDR 50-30 Silencieux

Silencieux rectangulaire - longueur: 950mm

.